Consolidation
point
Horizontal cabling
Telecommunications room
horizontal cross-connect
To equipment
Work area
cables
Open office area
Consolidation Point
To equipment
Open office area
Horizontal cabling
18
Black Box Guide to Structured Cabling
Section NameSection Name
Structured Cabling System
Open office cabling.
If you have an open office with lots of modular
furniture and anticipate lots of MACs, the TIA has
specified two horizontal cabling configurations for
you: the MUTOA and the Consolidation Point. Both
will enable you to keep your horizontal cabling
intact when your open office layout is changed.
Open office cabling is the only exception you’ll
find to the 5-meter rule for work area cables.
Open Office Horizontal Cabling Distances
Work Area, Patch, and
Horizontal Cable Maximum Work Area Equipment Cord Maximum
Length Cable Length (24 AWG) Combined Length
90 m (295.3 ft.) 5 m (16.4 ft.) 10 m (32.8 ft.)
85 m (278.9 ft.) 9 m (29.5 ft.) 14 m (45.9 ft.)
80 m (262.5 ft.) 13 m (42.6 ft.) 18 m (59.1 ft.)
75 m (246.1 ft.) 17 m (55.7 ft.) 22 m (72.1 ft.)
70 m (229.6 ft.) 22 m (72.1 ft.) 27 m (88.6 ft.)
MUTOA (Multiuser Telecommunications Outlet Assembly).
The MUTOA enables the terminations of multiple
horizontal cables in a common, permanent location,
such as a column, wall, or permanent furniture, close
to a cluster of work areas. Guidelines include:
• Locate multi-user telecommunications outlets
in a permanent location.
• Multi-user telecommunications outlets shall
not be installed in the ceiling.
• The maximum cable length is 20 meters (65.6 ft.).
• A maximum of 12 work areas can be served.
• Uniquely identify work area cables on each end.
Consolidation point.
The Consolidation Point (CP) is a straight-through
interconnection point in the horizontal cabling.
It provides another option for open office cabling
and is ideal for work areas that are frequently
reconfigured, but not as frequently as a MUTOA.
Specifications include:
• Only one CP is allowed per horizontal run
between the work area and telecommunications
room. Cross-connection between the cables
is not allowed.
• A CP should not be more than 15 meters (49.2 ft.)
from the telecommunications room.
• A CP can serve a maximum of 12 work areas.
Centralized fiber optic cabling.
Centralized fiber optic cabling, Annex A to the
TIA/EIA-568-B.1, gives you recommendations for
designing a fiber-to-the-desktop system. It centralizes
the fiber electronics instead of using electronics on
different floors. Recommendations include:
• To connect the fiber from the work area to the
equipment room, you can use either a splice or
interconnect in the telecommunications room.
• The distance for the total channel is 300 meters
(984.3 ft.), including the horizontal, intrabuilding
backbone, and patch cords.
• Fiber can be pulled through the telecommunications
room. The distance is limited to 90 meters (295.3 ft.).
• Cable can be 50- or 62.5-micron fiber.
• Allow for slack and sufficient space for the
addition and removal of cable, and conversion
to a full cross-connect system.
Work area
cables
MUTOA
Telecommunications room
horizontal cross-connect
NOTE: The maximum length for a work area cable is 22 meters (72.1 ft).
For fiber cable, any combination of horizontal, work area, patch,
and equipment cables may not exceed 100 meters (328 ft).
MUTOA