Structured Cabling System
Planning backbone cabling.
Backbone cabling provides the main information
conduit connecting all your horizontal cabling within
a building and between buildings. It’s the inter-
connection between telecommunication rooms,
equipment rooms, and entrance facilities. In large
organizations, you can connect multiple LANs with
a high-speed backbone to create large service areas.
Backbone cabling is specified in TIA/EIA-568-B.1
and includes:
• Cabling
• Intermediate and main cross-connects
• Mechanical terminations
• Patch cords or jumpers for backbone-
to-backbone connections
Another type of backbone is called a collapsed
backbone. This is usually a short backbone that has a
central router or switch interconnecting all the LAN
segments in a given building.
The main requirement of any backbone is that
it be able to support your current needs as well as
future applications. When planning your backbone,
take these factors into consideration.
Performance and applications. Plan on far more
bandwidth than you think you’ll ever need.
Site size and user population. Current size and
future growth requirements must be considered.
Plan your backbone to accommodate the maximum
number of connections anticipated in all telecommun-
ications rooms, equipment rooms, and entrance
facilities. You may want to consider installing extra,
unused copper or ”dark” fiber cable for future needs.
Distance. The distance you run your backbone will
most likely determine the type(s) of cable you use.
Redundancy and diverse path routing. Consider
diverse path routing for mission-critical systems. This
consists of running redundant backbones in separate
pathways far from each other. The redundant cables
should never be run in the same conduit. Although
they terminate at the same place, they will follow
different routes to get there, such as on different
sides of a building.
Useful life. Be aware of the minimum length
of time the backbone cabling is expected to serve.
Replacing backbone cable is inconvenient and
expensive.
Entrance facility
Work area
2000 m (6561.7 ft.)
campus backbone
Backbone Cabling Distances
Backbone cabling
Building 2
Entrance facility
Building 1
Telecommunications room
90 m (295.3 ft.)
horizontal cabling
300 m (984.3 ft.) building
backbone cabling