Advant
®
Smart Device (HART
®
) Interface User’s Guide
Section 2.2.1 Connecting to an Advant Controller 410 Subsystem
3BUR 001 085R0001 REV A 2-7
The 3BUC900041R0001 cable (8 meters) between the MVI serial port and the RS-232/485
converter has the following pin assignments:
The Black Box IC108A is configured in the following manner:
Always refer to the documentation that comes with the equipment for more information.
Table 2-7. 3BUC900041R0001 MVI Serial Port to RS-232/485 Converter Cable
Description
MVI DTE
(1)
9-pin Female D connector
(1) Pins 1 and 9 are not used/connected.
RS-232/485 Converter
25-pin Male D connector
RD 2 3
TD 3 2
DTR 4 20
GND 5 7
DSR 6 6
RTS 7 4
CTS 8 5
Table 2-8. Black Box IC108A Set-up Requirements
Function
Switch/Jumper
Settings
Configure RS-232 port as DCE XW1 in position A
RTS/CTS/CD delay W5 in position A-B
Signal ground not connected to frame
ground
W7 is OUT
Half-duplex operation (2-wire) W8 in position B-C
RTS/CTS delay - 0ms W9 in position C
RS-485 driver is RS-232 RTS/CD
enabled
W15 in position A-B
Half-duplex turnaround delay - 0.1ms W16 in position B
RS-485 Driver Enable Hold - 7ms W17 in position B
Normal Operation S1 in OUT position
RS-485 Receiver Terminated S2 in ON position
RS-485 Line Bias ON S3 in ON position
Kommentare zu diesen Handbüchern