Advant
®
Smart Device (HART
®
) Interface User’s Guide
Chapter 2 Installation
2-8 3BUR 001 085R0001 REV A
The Westermo Teleindustri AB MA-42 is configured in the following manner:
Always refer to the documentation that comes with the equipment for more information.
The twisted-pair RS-485 cable between the RS-232/485 converter and the first SHIM
connection has the following pin assignments:
Each subsequent SHIM on the RS-485 bus is daisy-chained to each other using a twisted-pair
wire connecting XTB1-8 to XTB1-8 and XTB1-9 to XTB1-9 of each SHIM.
Table 2-9. Westermo Teleindustri AB MA-42 Set-up Requirements
Function Switch Settings
Selection of power source
115V/230V AC
S1
is set according to
local AC requirement
Transmitter activated by RTS
CTS controlled by RTS
DCD controlled by RTS
CTS Delay = 20ms
S2
1,4,6 = ON
2,3,5 = OFF
2-wire Line Connection and Termination S3
2,5,6 = ON
1,3,4 = OFF
Table 2-10. RS-232/485 Converter to First SHIM Cable (RS-485)
Westermo Teleindustri AB
MA-42 Line Connection
(5-position screw terminal)
Black Box IC108A
TB1 (unterminated)
SHIM
XTB1 (unterminated)
Description
1,3 RxB, TxB 8 Data +
2,4 RxA, TxA 9 Data -