Advant
®
Smart Device (HART
®
) Interface User’s Guide
Chapter 3 Configuration
3-24 3BUR 001 085R0001 REV A
MAX DIGITAL GROUP
This is the maximum window size (words) for attempting to create a digital group output
command to the smart device.
Use the List function key (<F4>) to list the possible digital group sizes. Use the Up Arrow or
Down Arrow keys to highlight the value wanted, then press the Accept function key (<F8>) to
enter the value in the field.
The initial default value is 8.
The possible values are:
4 <- used for SHIMs
8
16
32
64
96
128
NOTE
The number entered in this field is the number of words, not channels.
AUTO SWAP BACKUP
This defines if there is an automatic swap to the back-up port when both ports are DOWN and
the “back-up port” comes up first.
Use the List function key (<F4>) to list the possible action of AUTO SWAP BACKUP. Use the
Up Arrow or Down Arrow keys to highlight the value wanted, then press the Accept function
key (<F8>) to enter the value in the field.
The initial default value is NO.
The possible values are:
NO <- used for SHIMs
YES