Section 4.3 Runtime Displays
3BUR 001 085R0001 REV A 4-5
4.2.2.3 Output Request Task
The output request task takes a request from the CCF output request queue and creates a
command request which is then sent to the transmitter via the transmitter queue. If grouping is
turned on it combines as many outputs as allowed into one command and places the request on
the transmitter queue. If any outputs are placed on the transmitter queue, the transmitter is
signalled to process it.
4.2.2.4 Transmitter Task
The transmitter takes requests off the transmitter queue allowing no more than one command to
be pending per smart device and sends the request to the appropriate port.
4.2.2.5 Receiver Task
The receiver takes the response from the smart device, determines whether there is a request
pending and that it matches with the response, updates the data base and flags CCF if the
response was to a digital read and any values have changed.
4.3 Runtime Displays
The runtime displays allow you to view parameter and status information for smart devices and
the SHIM they are connected to, as well as provide the capability to tune various configurable
parameters of a smart device.
Fields on the tuning displays contain either dynamic information (upper/lower range values,
primary value units, descriptor information, date, transmitter configurable message, and
damping value) or static information (digital value, command status, transmitter and CCF loop
tags, and sensor limits). The entries you make in these fields when changing a smart device’s
parameters depends on the type of field. For example, a data field such as for the damping value
requires a numeric entry while another field may provide a selection menu of available choices
such as PSI, LBS and so on for transmitter units.
4.3.1 Display Hierarchy
Runtime tuning of smart devices is accomplished through a series of hierarchical displays.
Specifically, the displays and the tuning information they provide are listed below:
Smart Device Network Overview
lists status of each SHIM connected to and configured for a particular Advant
Controller serial port as well as the number of smart devices connected to each
SHIM.
Smart Device I/O Display
lists data base information such as the device tag name, CCF tag name,
descriptor, and digitally read value for up to eight smart devices connected to a
particular SHIM.
Smart Device Tuning Overview
allows you to change the configuration parameters for a particular smart
device and download the changes to the smart device’s data base.