3-26 3BUR 001 085R0001 REV A
3.3.5.4 SMARTNET Object
The SMARTNET object is a child of the PLC_DEF object. SMARTNET objects define the
smart devices connected to each SHIM. The SMARTNET also defines the correlation between
the smart devices and the CCF channel numbers. One SMARTNET templet allowed per
PLC_DEF object of PLC TYPE = SHIM. The example of the SMARTNET object templet view
is shown in Figure 3-11. This object has the following configurable attributes:
TEMPLET NAME
The templet name is required on all templets in the Template Builder. Give the SMARTNET
templet a name that contains up to 21 characters. The name must be unique system wide.
NETWORK ADDRESS
ModbusB slave address set via the DIP switch labeled S1 on the SHIM. Valid entries are 1
through 31 regardless of whether the SHIM is connected to an MVI serial I/O port via RS-232
directly or through the converter for RS-485. The network address must match the STATION
address value entered in the PLC_DEF templet.
NOTE
You can connect only one SHIM directly with RS-232 to the serial I/O port. You
can connect up to 31 SHIMs to a serial I/O port of a via a RS-485 bus, however,
each SHIM on the RS-485 bus must have a unique address.