Advant
®
Smart Device (HART
®
) Interface User’s Guide
Chapter 3 Configuration
3-8 3BUR 001 085R0001 REV A
SOFTWARE NAME Field
This field specifies the software downloaded to the controller at start-up.
Valid entries are: AC460.
Default is: AC460
DO RATE Field
The DO RATE field specifies the minimum resolution of any pulse output for the controller. For
pulse train outputs, the pulse width and pulse interval as specified through the PO CHANNEL
NUMBER edit window of the Controller I/O Templet must be multiples of the DO Rate. For
pulse duration outputs, the duration value calculated by the Pulse Duration FCM is rounded to
the next lower multiple of the DO Rate.
Valid entry is:
a number of milliseconds as either 20, 40, 100, 200, or 1000
Default is: 20
NOTE
Digital inputs are scanned at one half the DO RATE. This is important because
using the DO RATE default value of 20 ms when no pulse outputs are present will
lead to a high CPU load. The scan rate for smart devices is not affected by the
DO RATE field.