Commissioning
Checking Input Connections
Single-Phase Generator &
Voltages Delivered by 2 VT
Description
Perform this check when:
b the input foltages are supplied by two VTs as a
set
b the VTs connect phase-to-phase in the primary
With this configuration, the residual voltage must be
obtained outside Sepam™ by using three VTs that
have their secondaries connected in a broken delta
arrangement.
You can also perform this check when the residual voltages are either:
b obtained by other means
b used for purposes other than protection (control, monitoring, alarm)
Block Diagram
DE50709
* Detection of Plugged Connector (required for proper operation. Installed manually)
Procedure
1 Connect the single-phase voltage and current generator to the corresponding test terminal boxes by using the plugs provided, according to
the block diagram.
2 Turn the generator on.
3 Apply (via the test box) the voltage delivered at the V-N terminals of the generator, set to 3/2 multiplied by the rated secondary phase-to-
phase voltage of the VTs (that is, 3 V
LL
s
/ 2) between terminals 1-2 of Sepam’s voltage inputs.
4 Inject the generator I current, set to the rated secondary current of the CTs (that is, 1A or 5A) and in phase with the V
Ln
voltage applied
(specifically, generator phase displacement α(V-N, I) = 0°) to Sepam’s phase a current input (via the test box).
5 Use the SFT2841 software to check the following:
b the value indicated for Ia phase current is approximately equal to the rated primary current of the CT (I
Np).
b the value indicated for Van phase-to-neutral voltage is approximately equal to the rated primary phase-to-neutral voltage of the VT
(V
Ln
p = V
LL
p / 3)
b the value indicated for the phase displacement ϕ1(V1, I1) between the Ia current and Va voltage is approximately equal to 0°
6 Proceed in the same way to check the Ib, Vb, ϕb(Vb, Ib) values:
b apply the generator V
Ln
voltage set to 3V
LLs
/ 2 in parallel between terminals 1-2 and 4-2 of Sepam’s voltage inputs (via the test box).
b inject a current set to 1A or 5A and in phase opposition with the V
Ln
voltage
(that is, α(V
Ln
, I) = 180°) to Sepam’s phase b current input (via the test box)
b obtain Ib INp, Vbn V
Ln
p = V
LL
p/3 and ϕb . In the absence of residual voltage, Vbn = 0, Vab = 3V
LLp
/ 2
7 Check the Ic, Vcn, ϕc(Vcn, Ic) values as well:
b apply the generator V
Ln
voltage set to 3V
LLs
/ 2 between terminals 4 and 2 of Sepam’s voltage inputs (via the test box)
b inject a current equal to 1A or 5A and in phase with the V
Ln
voltage (namely, α(V
Ln
, I) = 0°) to Sepam’s phase c current input (via the
test box)
b obtain Ic INp, Vcn V
LnL
p = V
LL
p / 3 and ϕc 0°. In the absence of residual voltage, Vcn = 0, Vab = 3V
LLp
/ 2
8 Turn the generator off.
Ia
Ib
Ic
Van
Vbn
Vcn
Va
Vr