Installation
MES120, MES120G, MES120H
14 Input/6 Output Modules
Installation
Connection
The inputs are potential-free and the DC power supply source is external from the
relay base unit.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
b Only qualified electrical workers should install this equipment. Such work
should be performed only after reading this entire set of instructions.
b NEVER work alone.
b Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
and tagged. Pay particular attention to the design of the power system.
Consider all sources of power, including the possibility of backfeeding.
b Always use a properly rated voltage sensing device to confirm that all
power is off.
b Screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.
DE51645
Connector Wiring
Wiring without fittings:
b one wire with maximum cross-section 0.2 to 2.5 mm² (≥ AWG 24-12)
b two wires with maximum cross-section 0.2 to 1 mm² (≥ AWG 24-16)
b stripped length: 8 to 10 mm (0.31 to 0.39 in)
Wiring with fittings:
b Recommended wiring with Telemecanique fittings:
v DZ5CE015D for one 1.5 mm² wire (AWG 16)
v DZ5CE025D for one 2.5 mm² wire (AWG 12)
v AZ5DE010D for two 1 mm² wires (AWG 18)
b tube length: 8.2 mm (0.32 in)
b stripped length: 8 mm (0.31 in)
b Tightening torque: 6.1 to 8.8 in-lb (0.7 to 1 Nm)
* Ox01 denotes module number of I/O. For example, the first output of module #2 is O201. See page 22 of this manual.