Installation
Base Unit
Connecting Phase Current Inputs
Variant 1: Measuring Phase Current by three - 1A or 5A CTs (Standard Connection)
DE80089
Description
Connecting three - 1A or 5A sensors to the CCA630 or CCA634 connector.
Calculate residual current by measuring the three-phase currents.
Parameters
Sensor type 5A CT or 1A CT
Number of CTs Ia, Ib, Ic
Rated Current (I
N) 1A to 6250 A
Variant 2: Measuring Phase Current by two - 1A or 5A CTs
DE80088
Description
Connecting two - 1A or 5A sensors to the CCA630 or CCA634 connector. All
protection functions are based on monitoring phase A and phase C currents.
Phase current IB is assessed only for metering functions (assuming Ir = 0).
The user cannot calculate residual current or use ANSI 87T and 87M differential
protection functions on the Sepam™ T87, M87, M88, G87 and G88 under this
configuration.
Parameters
Sensor type 5A CT or 1A CT
Number of CTs Ia, Ic
Rated Current (I
N) 1A to 6250 A
CCA630/
CCA634
Ib
Ic
a
b
c
Ia
Variant 3: Measuring Phase Current with three LPCT Type Sensors
DE51790
Description
The CCA671 Connector uses three Low Power Current Transducer (LPCT) type
sensors to keep Sepam™ from going into a fail-safe condition.
There are three sets of Dual In-Line (DIP) switches, shown at the bottom of the
CCA671 example to the left, one set for each phase. Each of these is set for the Full
Load Amps (FLA) for that phase.
Calculate residual currentby measuring the three phase currents Ia, Ib, and Ic. They
are measured by 3 x 1A or 5A CTs or by three LPCT type sensors.
LPCT sensors cannot be used to obtain the following measurements:
b Phase current measurements for Sepam™ T87, M88 and G88 with ANSI 87T
transformer differential protection (connectors and )
b Phase current measurements for Sepam™ B83 (connector )
b Unbalance current measurements for Sepam™ C86 (connector ).
Parameters
Sensor type LPCT
Number of CTs Ia, Ib, Ic
Rated Current (I
N) 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000,
1600, 2000 or 3150 A
Note : Rated Current (I
N) must be set twice, because:
b The software parameter setting uses the advanced UMI or the SFT2841 software tool.
b The hardware parameter setting uses microswitches on the CCA671 connector.
Ic
Ib
Ia
a
b
c
ab
c