54
© 2007 Schneider Electric. All Rights Reserved.
1
63230-216-229-B1
Installation
MCS025
Sync-Check Module
PE50285
Function
The MCS025 module checks the upstream and downstream voltages of a circuit
breaker to ensure safe closing (ANSI 25).
It checks the differences in amplitude, frequency, and phase between the two
measured voltages, and takes into account dead line/bus conditions.
Three relay outputs can be used to send a Close Enable signal to several
Sepam™ Series 80 units.
The circuit-breaker control function of each Sepam™ Series 80 unit takes this close
enable into account.
The settings for the sync-check function and the measurements carried out by the
module are accessed by the SFT2841 setting and operating software. They are
similar to the other settings and measurements for the Sepam™ Series 80.
The MCS025 module is equipped with the following:
b CCA620 connector for connecting the relay outputs and the power supply
b CCT640 connector for voltage connection
b CCA785 cord for connection between the module and the Sepam™ Series 80
base unit
MCS025 Sync-Check Module
Characteristics
MCS025 Module
Weight 2.98 lb (1.35 kg)
Assembly With the AMT840 accessory (must be ordered separately)
Operating temperature –13°F to +158°F (–25°C to +70°C)
Environmental characteristics Same characteristics as Sepam™ base units
Voltage Inputs
Input impedance > 100 kΩ
Burden < 0.015 VA (VT 100 V)
Continuous thermal withstand 240 V
1-second overload 480 V
Relay Outputs
Relay Outputs O1 and O2
Voltage DC 24/48 V DC 127 V DC 250 V DC
AC (47.5 to 63 Hz) 100 to 240 V AC
Continuous current 8 A 8 A 8 A 8 A
Breaking capacity Resistive load 8 A / 4 A 0.7 A 0.3 A
Load L/R < 20 ms 6 A / 2 A 0.5 A 0.2 A
Load L/R < 40 ms 4 A / 1 A 0.2 A 0.1 A
Resistive load 8 A
Load p.f. > 0.3 5 A
Making capacity < 30 A for 200 ms
Isolation of outputs from other
isolated groups
Enhanced
Relay Outputs O3 and O4 (O4 not used)
Voltage DC 24 / 48 V DC 127 V DC 250 V DC
AC (47.5 to 63 Hz) 100 to 240 V AC
Continuous current 2 A 2 A 2 A 2 A
Breaking capacity Load L/R < 20 ms 2 A / 1 A 0.5 A 0.15 A
Load p.f. > 0.3 5 A
Isolation of outputs from other
isolated groups
Enhanced
Power Supply
Voltage 24 to 250 V DC, -20 % / +10 % 110 to 240 V AC, –20 % / +10 %
47.5 to 63 Hz
Maximum burden 6 W 9 VA
Inrush current < 10 A for 10 ms < 15 A for one half period
Acceptable momentary outages 10 ms 10 ms