Use
Local Operation on the UMI
Types of Operations and Passwords
Types of Operations
The Sepam™ UMI can perform three types of operations:
b normal operations, such as consulting operating information, resetting
Sepam™ and current alarms acknowledgement
b protection settings, like modifying the tripping set point of an active protection
function
b modifying Sepam™ parameters: for example, change the operating language
or set the internal clock
Protection setting and parameter operations require a password.
Passwords
Protection setting and parameter operations are protected by two different
passwords, each having four digits:
b password for protection settings
b password for parameter settings
The default passwords are 0000.
The table below indicates the operations authorized for each password.
Operations No Password Protection-Setting
Password
Parameter-Setting
Password
Normal operation bbb
Set the active
protection functions
(1)
bb
Modify Sepam™
parameters
b
DE51564
Entering Passwords
Perform the following steps to enter a password:
1 Press to access the screen for password entry.
2 Press to position the cursor on the first digit.
3 Press the cursor keys and as needed to scroll through the digits.
4 Press to confirm and go to the next digit.
(Do not use characters other than numbers 0 to 9 for each of the 4 digits.)
5 After the four digits are entered, press to position the cursor on [Apply].
6 Press again to confirm.
Validating Passwords
Password Validity
After entering the protection-setting password, the icon displays at the top of
the screen.
After entering the parameter-setting password, the icon displays at the top of
the screen.
The icon remains displayed as long as the password is valid, and the corresponding
operations are authorized.
End of Validity
A password is deactivated either by pressing or automatically if no keys are
activated for more than 5 minutes.
Loss of Passwords
Contact a technical support representative for information.
(1) SFT2841 software required
Screen for password entry.
DE51565
Indication of password validity on the display:
= password for protection settings is valid.
= password for parameter settings is valid.